STI Vibration Monitoring, Inc. Vibration Monitoring & Machine Protection Systems
1010 East Main Street, League City, TX 77573
www.stiweb.com / www.stiwebstore.com
Tel 281.334.0766   
Toll Free 888.777.7213   
Fax 281.334.4255   
Sensors - Vibration Monitors - Vibration Transmitters - Protection Systems - Junction Boxes - BNC Switch Boxes - Sensor Cables - Mounting Hardware - Rotor Kits - Balancing Kits

Products

Vibration Calculator

Follow us on FacebookFollow us on TwitterSTI Vibration Monitoring YouTube

CMCP565A Isolated Thermocouple Temperature Monitors

Field Application Note: Differential Expansion TSI

Solid State Temperature Monitors

         Features:
  • Low Cost
  • Small Size
  • DIN Rail Mount
  • J or K Type Thermocouple Input
  • 4-20 mA Output
  • Fault Detection
  • Buffered Transducer Output
  • Filter Option
  • Alert and Danger Alarms
  • Trip Multiply
  • Remote Reset
  • CE Approved Approved

Download Data Sheet in PDF Format Manual Quick Start Tech Note CE Declaration CSA / UL Hazardous Area Approved

CMCP565A Isolated Thermocouple Temperature Monitors

CMCP500 Monitor Approval Label

Description:

The CMCP565A Isolated Thermocouple Temperature Monitor are compatible with type J and K thermocouple inputs, and they provide a 4-20 mA output proportional to the overall measurement. Each unit processes the signal to determine overall amplitude, and outputs a 4-20 mA dc current that is proportional to a user specified range such as 0-250 Deg. F. Combining monitors with an existing PLC or DCS system results in a high density, low cost monitoring system. The alarm feature functions as a complete single channel monitor that includes alert and danger alarms, and output relays.

Buffered Output:

A BNC connector mounted on the front of the unit provides access to the buffered transducer output signal. This includes both the unfiltered vibration signal, and the DC bias voltage. Portable test equipment or analyzers like SKF-CM's Microlog™ can be connected to this output without disturbing other system outputs.

Fault Detection:

On board fault detection circuitry continuously monitors the transducer for normal operation. If a fault occurs, the output current is reduced to 2 mA to indicate the fault to the readout system. A red LED on the front of the unit is turned on to provide a local indication of the fault.

Alarms:

The CMCP565A Series Monitors have two independent set points, with LED alarm indicators and output relay contacts (Alert and Danger). Set points are adjustable via potentiometer, from 0 to 110% of full scale. Each has an adjustable delay of 1 to 10 seconds. Relay contacts can be independently configured by the user for either Normally Open (NO) (Standard) or Normally Closed (NC) operation. Relays are normally de-energized and can be configured for latching or non-latching (standard) operation. Latched alarms may be reset locally or by remote contact closure. SPST Relay contacts are rated 5 Amps @ 30 Vdc or 250 Vac for resistive loads. The monitors also have set point multiplication of 3X via contact closure (2X available).

Displays And Assemblies:

Various display options, NEMA and explosion-proof enclosures, and assembled multi-channel systems are available. Consult your sales representative.

Electrical Specifications:

Power: +24 Vdc @ 45 mA max. (30 mA typical at 2 full scale output). Reverse polarity and transient protection   included.(With the Alarm/Relay option installed: 75 mA max.)
Frequency Response (Without optional filters): (-3 dB) 2 Hz to 20 kHz.
Buffered Output: BNC Connector 0-20 kHz.
Accuracy: 5.0 % of Full Scale Range.
Output: 4-20 mA proportional to the full scale range.
Maximum Load: 600 Ohms Resistive.
Case: Isolated.

Environmental Specifications:

Operating Temp.: -20°C to +80°C (-4°F to +176°F).
Storage Temp.: -55°C to +125°C (-67°F to +257°F).
Relative Humidity: 0 - 95% Non-Condensing

Mounting:

32 mm (G style) or 35 mm (T style) DIN Rail.

Ordering Example:

To order a thermocouple temperature monitor that accepts input from a J type thermocouple, with a Full Scale of 0-250° F, specify Part Number: CMCP565A-J-01.

NOTES:

1.The Full Scale option specified at order entry is used by the factory for initial calibration. However, several other ranges can be jumper selected in the field.

2.Transducer and Full Scale options not listed in the above table are available. Contact your sales representative.


CMCP565A Thermocouple Temperature Monitor
CMCP565A-(a)-(bb)

(a) Input
J, J Type Thermocouple
K, K Type Thermocouple

(bb) Full Scale
01, 0-250 °F
02, 0-350 °F
03, 0-500 °F
51, 0-120 °C
52, 0-175 °C
53, 0-260 °C

 

Copyright © 2014 STI Vibration Monitoring Inc. All Rights Reserved.