Tech Note 109
Troubleshooting 500 Series Transmitters

Field Application Note: Differential Expansion TSI
OK Light Off:
  1. • Check +24VDC Power at bottom left terminals
  2. • Check to be sure Sensor is wired properly to top left terminals.
  3. • OK Light will turn on after 30 seconds if sensor is OK.
  4. • If OK Light stays out, check sensor bias or replace sensor
    1. • Accelerometer DC Bias should be between 4.0 to 16.0 VDC
    2. • Eddy Probe DC Gap should be between -3.0 and -18.0 VDC
  5. • If sensor is good (DC bias or gap OK) replace transmitter.
No 4-20 mA Output:
  1. • Check to be sure OK Light is “On” (see above)
  2. • Disconnect field wires and verify 4-20 mA directly with Digital Volt Meter.
  3. • If OK Light is “On” and there is no 4-20 mA output replace transmitter.
Erratic or Noisy Readings:
  1. • Check to be sure sensor shield is landed with sensor common.
  2. • Verify sensor shield is not grounded at each end.
  3. • Check for ground loops in system.
  4. • Verify sensor and cabling installation is in conduit and away from AC power.
  5. • If radios are causing interference, be sure to use metal enclosure and conduit.