CMCP500 (A) Series Monitors
may be wired either with individual alarms or with common alarm outputs
grouped by machine or system. When wiring common alarms the OK (normally
energized) circuit is wired in series using the normally closed (NC) contacts.
On a loss of sensor Ok or power the OK relay will change state opening the
circuit. Closed = OK, Open = Not OK.
As an alternative the
OK circuit could also be wired in parallel (as Alert and Danger are shown)
using the normally open side of the relay in which case. Open = OK, Closed
= Not OK.
Alert and Danger common alarms
(normally de-energized) are usually wired in parallel using the normally
open (NO) contacts. An alert or danger vibration alarm will close the respective
circuit. Open = No Alarm, Closed = Alarm.
On CMCP500 Series Monitors the
OK relay is normally energized and the Alert and Danger relays are normally
de-energized.
On all CMCP500 Series Monitors
the OK relay terminals are located on the lower right front and the Alert
and Danger relay terminals are found on the pluggable terminal located on
the bottom of the monitor.
Common Alarm Example:  |