STI Vibration Monitoring, Inc. Vibration Monitoring & Machine Protection Systems
1010 East Main Street, League City, TX 77573
www.stiweb.com / www.stiwebstore.com
Tel 281.334.0766   
Toll Free 888.777.7213   
Fax 281.334.4255   
Sensors - Vibration Monitors - Vibration Transmitters - Protection Systems - Junction Boxes - BNC Switch Boxes - Sensor Cables - Mounting Hardware - Rotor Kits - Balancing Kits

Products

Vibration Calculator

Follow us on FacebookFollow us on TwitterSTI Vibration Monitoring YouTube

Tech Note 110
Troubleshooting CMCP420VT Series

Field Application Note: Differential Expansion TSI

Bench testing a CMCP420VT(T) is quite easy and can be accomplished using a 24 VDC power supply and a DVM (Digital Volt Meter) in mA (Amp) mode. Be sure that the fuse in the mA input of your DVM is good. Most quality DVM’s have a 1 and 10 Amp selection. Select the lowest as you will only be measuring to about 30 mA or 0.030 Amp. Be sure the power supply is wired plus to plus and minus to minus to the CMCP420VT. The DVM can be inserted in series in either leg.

***** Important *****
The CMCP420VT requires a minimum voltage dependant on resistance in the loop. If units locks at >21 mA voltage needs to be increased by using an external +24 VDC power supply.

In the case of the CMCP420VT-T with Temperature the loop mA is checked the same way, just move the wires to the temperature side of the terminal. Heat the unit gently with a heat gun or your hand and mA output will increase. Allow time for unit to heat soak and do not overheat.

The CMCP420VT will begin operation as soon as 24 VDC power is supplied. Start up time is short but give the unit about 30 seconds for the integrator to settle. At rest on a table or desk top the unit should read about 4.0 mA (0.004 Amp) depending on floor and table vibration. Tap the unit gently against the table at a rate of a couple times per second. Increasing the force of the taps will cause the unit to read over 20 mA (0.020 Amps).

CMCP420VT Bench Test Setup

Problem

Solution

No Output

Verify Wiring
Verify Supply Voltage at V+ Terminal (18 to 36 VDC)
Verify Loop with DVM in Series (mA Mode)
Verify PLC/DCS Scaling (4 mA = 0, 20 mA =1.00)
Verify External Power Supply Common is Established (If Used)
Replace with Spare

Output Locked at >21 mA

Inadequate Supply Voltage
Verify Supply Voltage at V+ Terminal (18 to 36 VDC)
Increase Supply Voltage as Required

Low Vibration Reading

Verify with Portable Meter
Verify PLC/DCS Scaling (4 mA = 0, mA =1.00)
Verify Sensor is Correctly Positioned on Bearing

High Vibration Reading

Verify with Portable Meter
Verify PLC/DCS Scaling (4 mA = 0,20 mA =1.00)
Repair Machine or Adjust Process

Erratic Measurement

Verify with Portable Meter
Verify Unit is Mounted Securely
Verify Wiring and Intermediate Terminals

 

 

Copyright © 2014 STI Vibration Monitoring Inc. All Rights Reserved.